Eland A9SWA4040LSZH
0.6/1KV Power & Control Cable, 4X4.0§±, XLPE Insulation, LSZH Out Sheath
Applications
SWA Cable – power and auxiliary control cables use in power networks, underground, outdoor and indoor applications and use in cable ducting. installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment.
Standards
BS6724, IEC 60502-1, IEC 60754-1 and 2 BS EN 50267-2-1 and 2, BS EN / IEC 61034-1
Technical Data
Conductor : Class 2 plain stranded copper conductor to BS EN 60228:2005 (previously BS6360)
Insulation : XLPE (Cross-Linked Polyethylene)
Bedding : LSZH (Low Smoke Zero Halogen)
Armouring : Single Core: AWA (Aluminium Wire Armour), Multi-Core: SWA (Steel Wire Armour)
Sheath : LSZH (Low Smoke Zero Halogen)
Sheath Colour : Black (Carbon loaded UV stability)
Voltage Rating : 600/1000V
Temperature Rating : 0¡ÆC to +90¡ÆC
Minimum Bending Radius : 1.5mm2 - 16mm2: 6 x overall diameter / 25mm2 and above: 8 x overall diameter
Core Identification
1 Core: Brown
2 Cores: Brown, Blue
3 Cores: Brown, Black, Grey
4 Cores: Blue, Brown, Black, Grey
5 Cores: Green/Yellow, Blue, Brown, Black, Grey
Alternative core identification: White cores with Black numbers
Dimensions
BS6724 XLPE/LSZH/AWA/LSZH (Copper)
Eland Part Number : A9SWA4040LSZH
No. of Cores x Nominal Cross Sectional Area # x mm©÷ : 4 X 4.0
Nominal Thickness of Insulation mm : 0.7
Nominal Diameter mm : Under Armour( 11.0 ) / Overall( 16.4 )
Nominal Weight kg/Km : 532
BW/ CW : 20/20
Wraparound cleats : CC7
========================================================================================== ÄÉÀ̺í Åø www.CableTool.co.kr (Ư¼ö»ç¾ç ÄÉÀ̺í), www.CableTool.kr (¼îÇθô-º§µ§ ¿µ»ó, À½Çâ ÄÉÀÌºí ¼Ò·® ÆǸÅ) ÄÉÀ̺í Åø ±â¼ú¹®ÀÇ ¿¬¶ôó / Ư¼öÄÉÀ̺í T.0707-434-7711 / ÄÉÀ̺í T.7712 / ÄܳØÅÍ T.7713 / Åø T.7714ÄÉÀ̺í Åø, ÄܳØÅÍ, Åø Àç°í ¹× °ßÀû ¹®ÀÇ / T.7715(Ãæû, °æ»ó, Àü¶ó) / 7716(¼¿ï, °æ±â) / M.010-7196-2171ÄÉÀ̺í ÅøÀº ÅÛÇöóÀÌÇÁ ¼±¹«µµ www.TempleLife.kr ¸¦ ÈÄ¿ø ÇÕ´Ï´Ù. TempleLife with Sunmudo
|